Power Distribution & Current Draw

Real-world amplifier current per phase, breaker loading and generator size.

System load

sum of all channels at their load
W
W
A

Results

Average current per phase
8.3A
Peak-ish current per phase
16.6A
Breaker loading (avg)
26%
Average mains power
5.13kW
Generator size (with 25 % margin)
14.4kVA
Amp mains draw at duty
3.13kW
Comfortable: average draw is under 80 % of the breaker rating with peak headroom.

Phase loading

L18.3 AL28.3 AL38.3 A32 A breaker80 %solid = average · faint = peak

How it works

Amplifier spec sheets quote output power, not mains draw. Music is dynamic, so a 10 kW rig rarely pulls 10 kW from the wall: the industry rule of thumb is 1/8 of rated power for normal music (the standard for thermal testing), 1/3 for heavily compressed material. Divide by the amplifier's efficiency to get the mains power.

Formulas
P_mains = (P_rated × duty) / efficiency + other loads
I_phase = P_mains / (phases × V × PF)
20000 W × 0.125 / 0.8 + 2000 W = 5125 W → 8.3 A per phase
  • Inrush: big toroidal power supplies draw many times their running current for a few cycles at switch-on. Use sequencers and D-curve breakers.
  • Balance the phases: put subs, tops and lighting across different legs so no single breaker carries the bass bumps.
  • Generators dislike low power factor and non-linear loads. Oversize by at least 25 % and prefer a unit rated for entertainment use with good voltage regulation.
  • Cable and connector ratings (16 A CEE, 32 A, 63 A…) must match the breaker, not the other way round.